Conduit Fill Calculator Canada (CEC Raceway Fill Calculator)

Based on CEC 2024 Table 9G (conduit) and Table 6A (insulated conductor area), with Rule 12-910 fill limits. Select wire insulation, AWG/kcmil size, and conduit type.

Conductors

Pick insulation type (Table 6A) and conductor size for each row.

Conduit / Tubing

Choose raceway type (Table 9G) and trade size.

Ampacity Derating — CEC Table 5C

Rule 4-004(2): correction for more than 3 current-carrying conductors in a raceway or cable.

Applied factor

100%

Based on 3 conductors entered above. Count only current-carrying conductors when applying in the field.

# of current-carrying conductorsAmpacity correction
1 – 3100%
4 – 680%
7 – 2470%
25 – 4260%
43 and above50%

Apply this factor to the Table 2 (or applicable) ampacity before continuous-load adjustments. Neutrals of balanced 3-wire and 4-wire wye circuits are not normally counted; harmonic-rich loads may require counting per Rule 4-004(3). Always confirm against the current CEC.

Derated Ampacity — CEC Table 2 (Copper, in raceway)

Base ampacity × Table 5C correction factor (30 °C ambient).

ConductorTemp col.Base ampacity× 100%Derated ampacity
12 AWG TWN75 / T90 Nylon90 °C40 A× 1.0040 A

Values from CEC Table 2 (copper, not more than 3 conductors in a raceway, 30 °C ambient). The derated value above already accounts for Table 5C. Apply additional Table 5A correction if ambient differs from 30 °C, and respect Rule 4-006: equipment termination temperature (typically 75 °C) caps the usable ampacity regardless of the conductor's insulation rating.