Grounding & Bonding Conductor Size Calculator Canada (CEC)

CEC Table 16 — minimum bonding conductor and equipment grounding conductor size based on service rating and overcurrent device.

Ampacity of the largest ungrounded service/feeder conductor.

Rating/setting of breaker or fuse protecting the circuit (sizes the EGC).

Minimum bonding conductor
#6 AWG
Based on 200 A service · CEC Table 16
Equipment grounding conductor
#6 AWG
Based on 200 A OCPD · CEC Table 16
Note: where bonding conductors are run in parallel, each must be sized per Rule 10-814. Always verify against CEC Part I, Tables 16 / 16A and local amendments.

CEC Table 16 (reference)

Max OCPD / conductor (A)CopperAluminum
15#14 AWG#12 AWG
20#12 AWG#10 AWG
60#10 AWG#8 AWG
100#8 AWG#6 AWG
200#6 AWG#4 AWG
300#4 AWG#2 AWG
400#3 AWG#1 AWG
500#2 AWG#1/0 AWG
600#1 AWG#2/0 AWG
800#1/0 AWG#3/0 AWG
1000#2/0 AWG#4/0 AWG
1200#3/0 AWG250 kcmil
1600#4/0 AWG350 kcmil
2000250 kcmil400 kcmil
2500350 kcmil600 kcmil
3000400 kcmil600 kcmil
4000500 kcmil750 kcmil
5000700 kcmil1200 kcmil
6000800 kcmil1200 kcmil